LIGHTNING SURGE PROTECTOR FOR POWER SUPPLY (2A)
Model : MA-200
( 2A, 200V/220V/240V AC line voltage use )
Functions & Features :-
• Designed specifically for AC power supplies up to 2 amps
• No degradation of normal (50/60 Hz) line frequency
• Power indicator lamp provided
Specifications are subject to change without notice.
General Specifications :-
- Construction : Plug-inConnection: M3.5 screw terminals (chromated
steel; torque 0.8 N·m)
- Housing materia l: Flame-resistant resin (black)
- Monitor lamp : Green neon lamp turns on when the power is supplied.
Installation :-
- Operating temperature: -5 to +55°C (23 to 131°F)
- Operating humidity: 30 to 90% RH (non-condensing)
- Mounting : Surface or DIN rail
- Dimensions : W50×H85×D119.5 mm
(1.97”×3.35”×4.70”)
- Weight : 330 g (0.73 lbs)
Performance :-
Between Lines Line
To Gnd
- Discharge voltage
410V min.
410V min.
(peak voltage)
- Max. surge voltage*
700V max. 700V max.
(peak voltage)
- Leakage current
≤1mA
≤1mA
@300V DC
@300V DC
- Rated line voltage
200V AC
----
220V AC
----
240V AC
----
- Response time
≤0.1 μsec.
- Discharge current
1000A (8 / 20 μsec.)
- Max. load current
2A
- Voltage drop
≤2V (50/60 Hz)
*The maximum voltage that could pass through the surge protector.
Protected equipment must be able
to withstand this voltage for a very
short time period.
Standards & Approvals :-
- CE conformity: EMC Directive (2004/108/EC)
- EN 61000-6-4 (EMI)
- EN 61000-6-2 (EMS)
- Low Voltage Directive (2006/95/EC)
- EN 61010-1
- Installation category II
- Pollution degree 2
- Max. operating voltage 300V

I/P Transducer
Model : VP-6-J
Functions & Features
• Converting a DC input into a proportional standard pneumatic
signal
• Semiconductor pressure sensor in the feedback circuit
• High resolution
• No mounting position effect
• High-density mounting
Typical Applications
• Converting a 4 – 20mA from a PID controller into a
pneumatic signal
Model
Input
Power Input
Options
AC Power
DC Power
• Output
VP A : 4 – 20mA DC
B : 100V AC
S : 12V DC
(blank): 0.2 – 1.0 kgf/cm2
6 : 1 – 5V
DC C : 110V AC
R : 24V DC /A1S : 19.6
– 98.1 kPa
D : 115V AC
V : 48V DC /A2S : 20 –
100 kPa
F : 120V AC
/A3S : 20.7
– 103.4 kPa
G : 200V AC
/A2 : 0.2 – 1.0 bar
H : 220V AC
/A3 : 3 – 15 psig
J : 240V AC
• Pneumatic Connection: Rc 1/4" standard
/P7 : 1/4" NPT fitting
Input & Output :-
- Input :
• DC Current: 4 – 20mA DC; shunt resistor
attached to input terminals (0.5W)
Input resistance: 250W
• DC Voltage: 1 – 5V DC
Input resistance: 1MW minimum
- Output : 19.6 – 98.1 kPa, 0.2 – 1.0 kgf/cm2
20 – 100
kPa, 0.2 – 1.0 bar
20.7 –
103.4 kPa, 3 – 15 psig
The output goes below 0% if the input loop is open.
- Maximum air delivery : 60 Nl/minute (2.1 SCFM)
- Maximum air exhaust : 60 Nl/minute (2.1 SCFM)
General Specifications :-
- Construction : plug-in
- Material : Housing: flame-resistant resin (black)
Base
socket: die cast aluminium
Valve
section: die cast aluminium
Screw
terminals: nickel-plated steel; torque £0.8 N·m
- Connection : Input & power input: M3.5 screw terminals
Pneumatic: Rc 1/4" or 1/4" NPT female; torque £12
N·m
- Isolation : input to power
- Front adjustments : zero and span; ±5%
- Power input : AC : operational voltage range: rating ±10%,
50/60 ±2 Hz, approx. 2VA
DC : operational voltage range: rating ±10%,
(ripple 10% p-p max.),
approx. 1W (30mA at 24V)
- Operating temperature : -5 to +60°C (23 to 140°F)
- Operating humidity : 30 to 90% RH (non-condensing)
- Mounting : surface
- Dimensions : W54´H101´D146.5 mm
(2.13"´3.98"´5.77") excluding fitting and input resistor
- Weight : 750 g (1.65 lbs)
Installation :-
- Supply pressure: 140 kPa (1.4 kgf/cm2, 1.4 bar, 20 psig) ±10%
Use dry air containing no carbon black or other foreign
particles. To ensure reliability use an
air filter (0.01 microns). Air consumption : 6 Nl / minute (0.21 SCFM)
Performance in percentage of span :-
- Accuracy : ±0.3% including linearity and repeatability
- Linearity : ±0.2%
- Repeatability : 0.1%
- Temp. coefficient : ±0.05%/°C (±0.03%/°F)
- Mounting position effect : ±0.1% (all dimensions)
- Response time : £3 seconds (0 – 90%)
- Line voltage effect : ±0.1% over voltage range
- Insulation resistance : ³100MW with 500V DC
- Dielectric strength : 2000V AC @1 minute (input to power to
housing)

P/I Transducer Model : PV-A-J
Functions & Features :-
• Converting a standard pneumatic signal into a proportional DC
output • High-density mounting.
Typical Applications :-
• Converting a pneumatic system into a 4 – 20mA for
indicating and controlling in DCS system
Model
Output
Power Input
Options
Current
(DC) Voltage (DC)
AC Power
DC Power
PV A : 4 –
20mA
1 : 0 –
10mV B : 100V AC
S : 12V DC Pls refer ' *'
B : 2
– 10mA
2 : 0 – 100mV C : 110V AC
R : 24V DC
stated below
C : 1
– 5mA 3 : 0
– 1V
D : 115V AC V : 48V DC
D : 0
– 20mA
4 : 0 – 10V F :
120V
AC
E : 0
– 16mA
5 : 0 – 5V
G : 200V AC
F : 0
– 10mA
6 : 1 – 5V
H : 220V AC
G : 0
– 1mA 4W
: -10 – +10V J : 240V AC
Z :
Specify
0 : Specify
current
voltage
' * ' :
• Input :
(blank) : 0.2 – 1.0 kgf/cm2
/A1S : 19.6
– 98.1 kPa
/A2S : 20 – 100 kPa
/A3S : 20.7 – 103.4
kPa
/A2
: 0.2 – 1.0 bar
/A3 : 3
– 15 psig
• Pneumatic Connection : Rc 1/4" standard
/P7 : 1/4" NPT fitting
Input & Output :-
- Input : 19.6 – 98.1 kPa, 0.2 – 1.0 kgf/cm2
20 – 100 kPa, 0.2
– 1.0 bar
20.7 – 103.4 kPa,
3 – 15 psig
- Output :
• DC Current : 0 – 20mA DC
Minimum span : 1mA
Zero suppression/elevation : max. 1.5 times span
Load resistance : output drive 15V maximum
Output
Load Resistance
4
– 20mA : 750 (W maximum)
2
– 10mA : 1500
1
– 5mA : 3000
0
– 20mA : 750
0
– 16mA : 900
0
– 10mA : 1500
0
– 1mA : 15k
• DC Voltage : -10 – +12V DC
Minimum span : 5mV
Zero suppression/elevation : max. 1.5 times span
Load resistance : output drive 10mA maximum;
5mA for negative voltage
output; at ³0.5V
Output
Load Resistance
0
– 10mV : 10k (W minimum)
0
– 100mV : 100k
0
– 1V
: 100
0
– 10V :
1000
0
– 5V
: 500
1
– 5V
: 500
-10
– +10V : 2000
General Specifications :-
- Construction : plug-in
- Material :
Housing:
flame-resistant resin (black)
Base
socket: die cast aluminium
Screw
terminals: nickel-plated steel; torque £0.8 N·m
- Connection :
Output & power input: M3.5 screw terminals
Pneumatic: Rc 1/4" or 1/4" NPT female; torque £12 N·m
- Isolation : output to power
- Front adjustments : zero and span; ±5%
Installation
- Power input :
AC : operational voltage range: rating ±10%, 50/60
±2 Hz, approx. 2VA
DC: operational voltage range: rating ±10% (ripple
10% p-p max.), approx.
2W (90mA at 24V)
- Operating temperature : -5 to +60°C (23 to 140°F)
- Operating humidity : 30 to 90% RH (non-condensing)
- Mounting : surface
- Dimensions : W54´H101´D138 mm
(2.13"´3.98"´5.43") excluding fitting
- Weight : 550 g (1.21 lbs)
Performance in percentage of span
- Accuracy : ±0.3%
- Temp. coefficient : ±0.03%/°C (±0.02%/°F)
- Response time : <= 1.5 seconds (0 – 90%)
- Permissible overrange : 196 kPa (2.0 kgf/cm2, 1.96 bar, 28 psig)
- Line voltage effect : ±0.1% over voltage range
- Insulation resistance : >= 100MW with 500V DC
- Dielectric strength: 2000V AC @1 minute (output to power to housing)

Differential RTD Transmitter Model : DR
Functions & Features :-
• Providing a DC output in proportion to the temperature
difference between two RTDs
• Isolation up to 2000V AC
• Fast response type available
• LCD meter (engineering unit display selectable)
• Simple loop test output (0% and 100%)
• High-density mounting
Typical Applications :-
• Measuring temperature difference between the inlet and outlet of
a heat exchanger
• Coolant
• Power plant (2000V AC isolation, 110V DC power supply)
Simple loop test output: 0% and 100% signal simulated by selecting the
front switch positions.
Model
Output
Power Input
Options
DR :
Current
Voltage
AC Power
DC Power
Non-isolated
A : 4 – 20mA DC
1 : 0 – 10mV DC B : 100V AC
S : 12V DC Pls refer to
below
B : 2 – 10mA DC 2
: 0 – 100mV DC C : 110V AC
R : 24V DC mark ' * '
C : 1 – 5mA DC
3 : 0 – 1V DC
D : 115V AC V : 48V DC
D : 0 – 20mA DC 4
: 0 – 10V DC
F : 120V AC P : 110V DC *1
E : 0 – 16mA DC
5 : 0 – 5V DC G :
200V AC
F : 0 – 10mA DC
6 : 1 – 5V DC H : 220V
AC
G : 0 – 1mA DC 0 : Specify voltage
J : 240V AC
Z : Specify current
' * ' -
/E : LCD meter (0.0 – 100.0%)
/E2 :
LCD display in engineering unit with backlight and the simple
loop test output
/K : Fast response (DRS only) *1
*1 : Not selectable with Option/E2.
INPUT RTD (two)
- 2-wire RTDs; JPt 100 (JIS ’89) or Pt 100 (JIS ’97, DIN,
IEC 751)
Remark : Pt 100 (JIS ’89) is deviated from Pt 100 (JIS
’97) only within the described accuracy
Input & Output :-
■ Input : 2-wire RTDs (two)
Maximum leadwire resistance : difference 0.5Ω
maximum between the transmitter and each RTD; each
leadwire resistance
10Ω or less
Sensing current : 2mA
Difference range : 0 – 20°C or 0 –
36°F (fixed)
Temperature range : 0 – 50°C or 32 –
122°F (fixed)
■ Output
• DC Current : 0 – 20mA DC
Minimum span : 1mA
Zero suppression/elevation : max. 1.5 times span
Load resistance : output drive 15V maximum
Output
Load Resistance
4 – 20mA :
750 (Ω maximum)
2 – 10mA :
1500
1 – 5mA
: 3000
0 – 20mA :
750
0 – 16mA :
900
0 – 10mA :
1500
0 – 1mA
: 15k
• DC Voltage : -10 – +12V DC
Minimum span : 5mV
Zero suppression/elevation : max. 1.5 times
span
Load resistance : output drive 10mA maximum;
5mA for negative voltage output; at ≥0.5V
Output
Load Resistance
0 – 10mV
: 10k (Ω minimum)
0 – 100mV :
100k
0 – 1V
: 100
0 – 10V
: 1000
0 – 5V
: 500
1 – 5V
: 500
General Specifications :-
- Construction : plug-in
- Connection : M3.5 screw terminals
- Housing material : flame-resistant resin (black)
- Isolation : input to output to power (non-isolated between I/O for DR)
- Overrange output : approx. -10 – +120% at 1 – 5V
- Front adjustments : zero and span; ±5%
- Display scaling : -10000 – +10000; ex-factory set to 0.00
– 100.00 (%)
- Engineering unit: %, μV, mV, V, mA, A, °C, °F, Ω or
DEG K, mHz, Hz, kHz, VAC, AAC, mg, g, kg, t,
rpm, rps selectable
Installation :-
- Power input :
AC : operational voltage range: rating ±10%,
50/60 ±2 Hz, approx. 2VA (approx. 3VA with Option /E2)
DC : operational voltage range: rating ±10%,
or 85 – 150V for 110V rating ripple 10% p-p max. approx. 2W
(80mA
at 24V; approx. 3W with Option /E2)
- Operating temperature : -5 to +60°C (23 to 140°F)
- Operating humidity : 30 to 90% RH (non-condensing)
- Mounting : surface or DIN rail
- Dimensions : W50×H80×D127 mm (1.97"×3.15"×5")
See General Spec. Sheet Figure A-1.
- Weight : 350 g (0.77 lbs)
- Terminal assignment : See General Spec. Sheet Figure B-1.
Performance in percentage of span :-
- Accuracy : ±0.2%*
- Display accuracy : ± (0.2% of FS + 1 digit)*
- Simple loop test output setting accuracy : ±0.5%
- Temp. coefficient : ±0.015%/°C (±0.008%/°F)
- Response time : ≤0.5 seconds (0 – 90%) approx. 25
milliseconds with option /K
- Line voltage effect : ±0.1% over voltage range
- Insulation resistance : ≥100MΩ with 500V DC
- Dielectric strength : 2000V AC @1 minute (DR: input or output to
power to ground)
*Temperature within 15 – 35°C or 59 – 95°F

RTD Transmitter Model
: RB
Functions & Features :-
• Accepting direct input from an RTD and providing a standard
process signal
• Linearization
• Burnout protection
• "Active bridge" circuit containing two constant current sources
allows large leadwire resistances up to 200Ω
• Isolation up to 2000V AC
• Fast response type available
• LCD meter (engineering unit display selectable)
• Simple loop test output (0% and 100%)
• High-density mounting
Typical Applications :-
• Long distance transmission between the RTD and the transmitter
• Combination with intrinsic safety barriers
• Power plant (2000V AC isolation, 110V DC power supply)
Model
Input
RTD
Output
Power Input
Options
( 2 or 3 wire )
Current
Voltage
AC Power
DC Power
Pls refer to ' * '
RB :
1 : JPt 100 (JIS ’89) A : 4 –
20mA DC 1 : 0 – 10mV DC
B : 100V AC S : 12V DC
mark below
( Non-isolated ) 3 : Pt 100 (JIS ’89)
B : 2 – 10mA DC 2 : 0 – 100mV
DC C : 110V AC R : 24V DC
4 : Pt 100 (JIS ’97, C : 1 –
5mA DC 3 : 0 – 1V DC
D : 115V AC V : 48V DC
DIN, IEC751 ) D : 0 – 20mA DC
4 : 0 – 10V DC F : 120V AC
P : 110V DC *1
5 : Pt
50Ω (JIS ’81) E : 0 – 16mA DC
5 : 0 – 5V DC
G : 200V AC
6 : Ni 508.4Ω
F : 0 – 10mA DC
6 : 1 – 5V DC
H : 220V AC
0 : Specify
G : 0 – 1mA DC
0 : Specify voltage J :
240V AC
Z : Specify current
' * ' :-
/E : LCD meter (0.0 – 100.0%)
/E2 : LCD display in engineering unit with backlight and the simple
loop test output
/K : Fast response (RBS only) *1
/BL : Downscale burnout
/UL : UL approval *2
*1 : Not selectable with Option/E2.
*2 : Not selectable with Option/E or /E2.
100V/110V/115V/120V AC power only.
Input & Output :-
■ Input : 2- or 3-wire RTDs
Maximum leadwire resistance : 200Ω per wire (3-wire)
Sensing current : 2mA (Pt)
Temperature range
RTD
Usable Range
Min. Span
°C
°F
°C
°F
JPt 100 (JIS ’89)
-200 to +500 -328
to +932 50 90
Pt 100 (JIS ’89)
-200 to +650
-328 to +1202 50 90
Pt 100 (JIS ’97/DIN/IEC) -200 to
+650 -328 to +1202 50
90
Pt 50Ω (JIS ’81)
-200 to +500
-328 to +932 100 180
Ni 508.4Ω
-50 to
+200 -58 to +392
30 54
■ Output :
• DC Current : 0 – 20mA DC
Minimum span : 1mA
Zero suppression/elevation : max. 1.5 times span
Load resistance : output drive 15V maximum
Output
Load
Resistance
4 – 20mA
: 750 (Ω maximum)
2 – 10mA
: 1500
1 – 5mA
: 3000
0 – 20mA
: 750
0 – 16mA
: 900
0 – 10mA
: 1500
0 – 1mA
: 15k
• DC Voltage : -10 – +12V DC
Minimum span : 5mV
Zero suppression/elevation : max. 1.5 times span
Load resistance : output drive 10mA maximum; 5mA for
negative voltage output; at ≥0.5V
Output
Load
Resistance
0 – 10mV
: 10k (Ω minimum)
0 – 100mV
: 100k
0 – 1V
: 100
0 – 10V
: 1000
0 – 5V
: 500
1 – 5V
: 500
General Specifications :-
- Construction : plug-in
- Connection : M3.5 screw terminals
- Housing material : flame-resistant resin (black)
- Isolation : input to output to power (non-isolated between I/O
for RB)
- Overrange output : approx. -10 – +120% at 1 – 5V
- Front adjustments : zero and span; ±5%
- Display scaling : -10000 – +10000; ex-factory set to 0.00
– 100.00 (%)
- Engineering unit : %, μV, mV, V, mA, A, °C, °F, Ω or
DEG K, mHz, Hz, kHz, VAC, AAC, mg, g, kg, t,
rpm, rps selectable
- Simple loop test output: 0% and 100% signal simulated by selecting
the front switch positions.
- Burnout protection : upscale standard; downscale optional
- Linearization : standard
Installation :-
- Power input :
AC : operational voltage range: rating ±10%,
50/60 ±2 Hz, approx. 2VA (approx. 3VA with Option /E2)
DC : operational voltage range: rating ±10%,
or 85 – 150V for 110V rating ripple 10% p-p max. approx. 2W
(80mA
at 24V; approx. 3W with Option /E2)
- Operating temperature : -5 to +60°C (23 to 140°F)
- Operating humidity : 30 to 90% RH (non-condensing)
- Mounting : surface or DIN rail
- Dimensions : W50×H80×D127 mm (1.97"×3.15"×5")
See General Spec. Sheet Figure A-1.
- Weigh t: 350 g (0.77 lbs)
- Terminal assignment : See General Spec. Sheet Figure B-1.
Performance in percentage of span :-
- Accuracy : ±0.2%
- Display accuracy : ± (0.2% of FS + 1 digit)
- Simple loop test output setting accuracy : ±0.5%
- Temp. coefficient : ±0.015%/°C (±0.008%/°F)
- Response time : ≤0.5 seconds (0 – 90%) approx. 25
milliseconds with option /K
- Burnout response : ≤10 seconds
- Line voltage effect : ±0.1% over voltage range
- Insulation resistance : ≥100MΩ with 500V DC
- Dielectric strength : 2000V AC @1 minute (RB:
input or output to power to ground)
Standards & Approvals :-
- Approval : UL/C-UL general safety requirements (UL 3111-1,
CAN/CSA-C22.2 No.1010-1)