ABB High Impedance Protection Relay

Model : SPAE010

Output contact ratings :-
Trip contacts, terminal numbers                                      : 65-66, 74 75
Rated voltage, make or break                                        : 250 Vac or dc
Make and carry for 0.5 s                                               : 30 A
Make and carry tor 3 s                                                  : 15 A
Continuous carry                                                           : 5 A
Breaking capacity for dc, when the control circuit time
constant L/R£ 40 ms, at 48/110/220 V dc                     : 5 A / 3A / 1 A
Contact material                                                            : gold plated AgNi
Signalling contacts, terminal numbers                              : 67-68-69,         70-71-72
Rated voltage, make or break                                        : 250 Vac or dc
Make and carry for O.5 s                                              : 10 A
Make and carry for 3 s                                                  : 8 A
Continuous carry                                                           : 5 A
Breaking capacity for dc, when the control circuit time
constant L/R £40 ms, at 48/110/220 V dc                     : 1A / 0.25A / 0.15A
Contact material                                                            : gold plated AgNi

Auxiliary power supply :-
Supply voltage, SPAE 010                                            : 80...265 V ac or dc
Power consumption                                                       : about 5 W

Insulation Tests :-
Dielectric test IEC 60255-5                                           : 2kV, 50Hz, 1min
Impulse voltage test IEC 60255-5                                  : 5kV, 1.2/50ms, 0.5J
Insulation resistance measurement IEC 60255-5             : >100MW, 500Vdc

Electromagnetic Compatibility Tests :-
High-frequency (1MHz) burst disturbance test
IEC 60255-22-1
- common mode                                                             : 2.5 kV
- differential mode                                                          : 1.0 kV
Electrostatic discharge test IEC 60255-22-2
and IEC 61000-4-2
- contact discharge                                                         : 6 kV
- air discharge                                                                : 8 kV
Fast transient disturbance test IEC 60255-22-4
and IEC 61000-4-4
- All ports                                                                       : 2 kV
Spark interference test voltage, inputs and outputs
as per SS 436 15 03, PL 4                                              : 4...8 kV

Environmental Conditions :-
Specified service temperature range                                  :  -10...+55°C
Transport and storage temperature range                          : -40...+70°C
Temperature influence on the operating values of the relay
over the specified service temperature range                     : <0.2%/°C
Damp heat test, cyclic IEC 60068-2-30                           : +25...55°C, r.h. > 93%, 6 cycles
Degree of protection by enclosure of the relay case
when panel mounted                                                         : IP 54
Weight of fully equipped relay                                           : 2 kg